Loss on ignition analyser PF1

TWO APPLICATIONS :
Measurement of the decarbonation rate at the bottom of the precalciner
PF1 KT
-> Optimization of the precalciner operation |
Measurement of the filler rate in the finished product flow
PF1 KF
-> Optimization of the filler rate in cement
|
Advantages :
- Automatic on-line equipment with integrated sample preparation, measurement and residues cleaning
- Output information used to control the precalciner and to optimize the burning operations
- Cost savings due to production increase combined with energy savings
- Quality enhancement of the finished product
- Possibility to use the same equipment to regulate the filler rate at the optimum level according to legislation
- Easy to install either on site or in automated laboratory
Principle :
- Sampling and transport systems are custom designed for each application:
- PF1 KT: air cooled piston sampler type PC303
- PF1 KF: screw sampling solution type PREC100 + P11
- Volumetric pre-weighing
- Precise sample weighing with an electronic scale
- Heating at 975 °C during 20 min
- Residual material weighing
- Analog 4-20 mA output (Profibus communication also available) to precalciner controls (KT model) or to the grinding mill control unit (KF model)
- Automated crucible cleaning system
- Pneumatic waste ejection
Performances :
- High frequency analysis : up to 2 analyses / hour
- No sample cross contamination
- Equipment adaptable to worldwide standards
- 3 operating modes: Automatic - Manual -Test
- High precision scale : 1/2500
- No loss of CO2 during sample transport to the analyser (KT model)
Specifications :
- Height : 1933 mm
- Depth : 833 mm
- Length : 1433 mm
- Weight : 500 kg
- Power supply : any from 380 to 600 V ; 50-60 Hz
- Compressed air supply : 6 bars, dry and clean
- Location : - close to the precalciner (KT model)
- in the cement laboratory (KF model)
|